Parameter sources

A parameter’s source says where its bytes come from and whether they can be written. Its value type then turns those bytes into the parameter’s value. The source is a JSON object; kind selects one of three sources:

kindBytes come fromWritable?
constA small value stored in the workspace under a keyWith allowWrite: true
calcA formula over other parameters’ valuesNever
modbus-tcpCoils or registers of a device, through an endpointHolding registers and coils, per writeFunction

Devices on a Modbus RTU (RS-485) bus are reached through a gateway that speaks Modbus TCP, such as an MC252: the parameter uses a modbus-tcp source on the gateway’s endpoint, with the device’s unit ID. Which source suits which need is explained in choosing a source.

Saving the setup rejects a source that refers to something missing or that does not fit, as described for each kind below. Device errors and formula failures that depend on the values appear only when the parameter is read or written.

{ "kind": "const", "key": "line-a.setpoint", "allowWrite": true }
FieldRules
key1–200 characters, naming the stored value in the workspace
allowWritefalse makes the parameter read-only: writes fail with not_writable
  • The stored value is at most 1,024 bytes. Until something is written, it is empty.
  • The parameter’s value type decodes the stored bytes, and a write stores the bytes it encodes.
  • Several parameters can share a key; they then read and write the same stored value.
  • The stored value is live data, not setup: hmi pull and hmi push sync the key, not the value.
{
"kind": "calc",
"inputParamIds": [
"11111111-1111-1111-1111-111111111111",
"22222222-2222-2222-2222-222222222222"
],
"formula": "#1 * 0.1 + #2",
"returnFormat": "float"
}
FieldRules
inputParamIds1–32 other parameters; their order defines #1 … #n
formula1–2,000 characters in the formula language, such as "#1 * 0.1 + #2"
returnFormat"int": a signed 32-bit integer; "float": a 64-bit IEEE 754 float, both big-endian
  • Each read reads the inputs, evaluates the formula, and packs the result into bytes that this parameter’s value type decodes. The value types that fit each returnFormat are in source bytes and value types.
  • A calc parameter is never writable: writes fail with not_writable.
  • Saving the setup, hmi push, and hmi check reject a formula that does not compile or refers to an input it does not have, such as #3 with two inputs (parameter_formula_invalid). They also reject a parameter that is its own input (parameter_input_self_reference), inputs that loop back to the parameter, even indirectly (parameter_input_cycle), and missing inputs (parameter_input_not_found).
  • A read fails when an input is disabled (param_disabled), when the formula fails on the values, such as a division by zero (formula_error), or when the chain of calc inputs is too deep (depth_exceeded).
{
"kind": "modbus-tcp",
"endpointId": "aaaaaaaa-aaaa-aaaa-aaaa-aaaaaaaaaaaa",
"unitId": 1,
"table": "holding-register",
"addresses": [100, 101],
"writeFunction": "multi-or-single-write"
}
FieldRules
endpointIdAn endpoint of the workspace
unitIdModbus unit ID, 0–255
tablecoil, discrete-input, holding-register or input-register
addresses1–64 addresses, each 0–65535; their number is the count
writeFunctionRequired for coil and holding-register; absent for the read-only tables
readOptional read settings

addresses are the zero-based addresses sent on the wire. Many device manuals number registers from 1, or in the “40001” style, so a holding register documented as 40001 is often address 0; the offset depends on the vendor.

The value type reads the bytes of the addresses in the order listed. Each register supplies two bytes, high byte first; each coil or discrete input supplies one byte, 0x00 when off or 0xff when on. To translate a manual’s word and byte order into value type settings, see byte relation.

Saving the setup, applying a template, hmi push, and hmi check reject a parameter whose addresses supply fewer bytes than its value type needs (modbus_source_too_short, with the available and required bytes). A float32 needs at least two registers and a float64 four; a byte filter that keeps one byte per register doubles that. More addresses than needed, and gaps in the list, are allowed. Strings, big integers, and ISO date strings have no minimum. An existing parameter with too few addresses does not block other saves, but saving that parameter fails until it is corrected; hmi check reports every such parameter, and hmi push refuses while any remains.

Saving also checks that the endpoint exists (parameter_endpoint_not_found). An endpoint that parameters still read from cannot be deleted (endpoint_in_use). While the endpoint is disconnected, reads and writes fail with endpoint_disconnected; the setup is unchanged.

writeFunctionWrites
noneNothing: the parameter is read-only
single-writeOne single-coil or single-register request per address
multi-or-single-writeOne multiple-write request for contiguous addresses, otherwise single writes. When the device answers Modbus exception 1 or 2 (illegal function or address), it writes the addresses one by one
always-multi-writeOne multiple-write request; addresses with gaps fail with sparse_write_unsupported

In a parameter template, writeFunction may be left out on coil and holding-register: applying the template sets multi-or-single-write. Templates set it only for another policy, such as single-write for a device that accepts only single-register writes.

Overvis combines reads of neighboring addresses of the same endpoint, unit ID and table into one request. read tunes this for one parameter; every field is optional. Setup has no controls for it: set it in a template, a pulled workspace, or through the API. Editing the parameter in Setup keeps it.

SettingDefaultMeaning
allowMultiReadtruefalse keeps this parameter out of combined reads
maxQuantityPerRequest50 registers, or 500 coils or discrete inputsThe most addresses in one request, at most 125 registers or 2,000 coils
atomictrue with several addresses, otherwise falseOne request must cover all the addresses, or the read fails with atomic_unsatisfiable
maxMergeGap0How many unread addresses may lie between combined spans (0–2,000)

Keep atomic: true when a value split across registers, such as a float, must not be read in two halves.

KindSetup controls
constKey, allow-write switch
calcOrdered input parameters (#1, #2, …), formula, result type
modbus-tcpEndpoint, unit ID, table, addresses, write function (for writable tables)

Changing the kind in Setup replaces the whole source with the defaults of the new kind; the value type stays as it was.