TR-101 Operating Manual

TR-101 Digital Temperature Relay

NOVATEK-ELECTRO LTD

Intelligent Industrial Electronics

DIGITAL TEMPERATURE RELAY TR-101

OPERATING MANUAL

Quality control system on the development and production complies with requirements ISO 9001:2015

Dear customer,

Company NOVATEK-ELECTRO LTD. thanks you for purchasing our devices.

You will be able to use properly the device after carefully studying the Operating Manual.

Keep the Operating Manual throughout the service life of the device.

UKRAINE, Odesawww.novatek-electro.com


This unit is safe for use in case of compliance with operating rules.

This manual is provided in order to introduce the operating personnel with structure, operating principle, design, mode of operation and maintenance of TR-101 digital temperature relay (further referred to as “device”, “TR-101” or “TR-101 unit”).

TR-101 complies with requirements:

  • EN 60947-1
  • EN 60947-6-2
  • EN 55011
  • EN 61000-4-2

No harmful substances in excess of the maximum permissible concentration is available.

TR-101 is designed for measuring and controlling a device temperature by means of four sensors connected according to a two- or three-wire diagram, with subsequent temperature display. The device can find various applications in industrial sector, in municipal utilities service, and agriculture.

The device allows for performing the following functions:

  • taking temperature measurement on 4 channels with use of standard sensors;
  • controlling temperature according to proportional-integral-differential (PID) principle;
  • temperature on-off regulation;
  • displaying currently measured temperature value on the integral LED digital display;
  • transferring the measured values for the sensors monitored via Modbus RTU standard protocol;
  • defining a break or a short circuit on the connected sensors lines;
  • measured temperature digital filtering and correction;
  • programming by the front panel keys and via PC; settings backup when de-energized;
  • settings protection from unauthorized change.

TR-101 has a flexible power supply and can use any voltage from 24 to 260 V, regardless of polarity.

TR-101 can use the following types of temperature sensors:

Table 1 – Supported Temperature Sensors

Sensor typeRated resistance at 0 °C, R0, OhmUSC notation (national)USC notation (international) W100=1.3850USC notation (international) W100=1.3910Temperature range
Platinum5050ПPt50Pt’50-50…+200 °C
Platinum100100ПPt100Pt’100-50…+200 °C
Platinum500500ПPt500Pt’500-50…+200 °C
Platinum10001000ПPt1000Pt’1000-50…+200 °C
Copper5050МCu50Cu’50-50…+200 °C
Copper100100МCu100Cu’100-50…+200 °C
Nickel100100НNi100-50…+180 °C
Nickel120120НNi120-50…+180 °C
Nickel500500НNi500-50…+180 °C
Nickel10001000НNi1000-50…+180 °C
Other990 at 25°C / 807 at 0°CPTC1000EKS111-50…+100 °C

2 Technical Specifications and Operating Conditions

Section titled “2 Technical Specifications and Operating Conditions”

Table 2 – Basic Technical Parameters

ParameterValue
Supply voltage24 – 260 V AC/DC
Recommended fuse1 A
Type of temperature measurement sensorsPt50, Pt100, Pt500, Pt1000, Cu50, Cu100, Ni100, Ni120, Ni500, Ni1000, PTC1000
Quantity of sensors connectable1 – 4
Sensors wiring schematic2 / 3 wires
Sensor wire length (2-wire)up to 5 m
Sensor wire length (3-wire)up to 100 m
Quantity of output relays4
Data memory≥ 10 years
Temperature measurement error± 2 °C
Measured temperature range-50 to +200 °C
Output relay testingavailable
RS-485 MODBUS RTUavailable
PID regulation with key element (relay)available
Two-position regulatoravailable
Channel measurement time≤ 0.6 sec
Protection degree: enclosureIP30
Protection degree: terminal blockIP20
Power consumption (under load)≤ 4.0 VA
Weight≤ 0.370 kg
Dimensions (H × W × D)90 × 139 × 63 mm
Output contacts electrical life (10 A, 250 V AC)≥ 100,000 cycles
Output contacts electrical life (10 A, 24 V DC)≥ 100,000 cycles
MountingStandard 35 mm DIN-rail
Mounting positionAny
Cos φMax. current at 250 V ACMaximum powerMax. voltage ACMax. current at 30 V DC
1.010 A4000 VA440 V3 A

The device is designed for operating in the following environment:

  • Ambient temperature: -35 to +55 °C
  • Storage temperature: -45 to +60 °C
  • Atmospheric pressure: 84 to 106.7 kPa
  • Relative air humidity (at temperature 35 °C): 30…80%

Trace of symbols at numeric display to letters of Roman alphabet is shown in Figure 3.

Display symbols mapping

Figure 3 – Trace of symbols at numeric display to letters of Roman alphabet

The device is manufactured in plastic casing (9 S-type modules) to be mounted onto standard DIN rail. The casing outline with overall and mounting dimensions is presented in Figure 3.1.

TR-101 dimensions

Figure 3.1 – TR-101 dimensions

Figure 3.2 presents the TR-101 front panel Exterior.

TR-101 front panel

Front Panel Elements:

  1. Currently displayed channel number indicator
  2. Seven-digit numerical display
  3. Up key (▲)
  4. Down key (▼)
  5. Enter key (ENTER), used in the device programming mode
  6. View mode and device programming mode enter key (MENU)
  7. RS-485 connection and communication activity indicator
  8. Parameter programming mode indicator
  9. Sensors failure indicator
  10. Relay close (open) indicator

Figure 3.2 – TR-101 Front Panel

In the menu mode, indicators (1, 7) display the corresponding parameter (on/off): rSA, ch1, ch2, ch3, ch4 (see Table 7.1).

Device control:

  • Use ▲▼ keys to toggle channels
  • Use MENU key to enter the parameter view mode
  • To enter the parameter edit mode – press MENU key and hold it within 7 seconds, the “setting” indicator (Fig. 3.2, item 8) shall light
  • To save modified value – use ENTER key
  • If no key has been pressed within 20 sec, TR-101 will display Ext sign (within 1 sec), and will switch to the initial state

3.2 Operating Principle and Input Signal Processing

Section titled “3.2 Operating Principle and Input Signal Processing”

In course of its operation, TR-101 performs input sensors scanning, then, based on the data obtained, calculates the current temperature value and outputs it on the digital display and sends control signals to the corresponding channel relay.

The signal that is received from sensor is transformed into a temperature digital value.

In order to eliminate the initial input signal processing error, as well as errors that are produced by the connection wiring, the device measured value can be adjusted. TR-101 provides for two adjustment types, which allow performing a gain shift or sloping by a specified degree for each channel independently.

3.2.3.1 Characteristic Shift

To provide for the error compensation ΔR = (R0 - R0.TC) produced by the input wiring resistance RTC, each measured temperature value (Tmeas) is added with a user specified value δ. Figure 3.3 shows an example of a characteristics shift for Pt100 sensor.

Programmable parameters: Sh1, Sh2, Sh3, Sh4

Characteristic shift

Figure 3.3 – Characteristic shift example for Pt100 sensor

3.2.3.2 Characteristic Slope

To provide for sensor error compensation upon W100 value deviation from the rated value, each Tmeas parameter measured value is multiplied by the user set adjustment parameter α.

The ratio boundaries are set within 0.50 to 2.00 limits. Figure 3.4 shows an example of the characteristic slant variation for Pt100 sensor.

Programmable parameters: KU1, KU2, KU3, KU4

Characteristic slope

Figure 3.4 – Characteristic slope example for Pt100 sensor

To provide for the input signal properties improvement the device employs digital filters that allow reducing the random interference effect on the temperature measurement.

Programmable parameters:

  • Digital filter band: Fb1, Fb2, Fb3, Fb4
  • Digital filter time constant: Ft1, Ft2, Ft3, Ft4

The filters are set for each input independently.

3.2.4.1 Digital Filter Band

The digital filter band allows protecting the measurement route from single interference and is set in °C. If the measured value Tmeas is different from the previous Tmeas–1 by the value larger than the Fb parameter value, the device assigns to it a value equal to (Tmeas + Fb). Thus the characteristic is smoothed out.

Smaller band width of the filter leads to slowing down the device reaction to temperature change. That is why in case of low interference level or during operation with discontinuous temperatures it is recommended to increase the parameter value or switch off the filter band action by setting the Fb1 (Fb2, Fb3, Fb4) parameter value to 0.

When working under strong interference, in order to eliminate its impact onto the device operation, it is necessary to reduce the parameter value.

3.2.4.2 Digital Filter Time Constant

The digital filter eliminates the noise signal components by smoothing it exponentially. The main characteristic of the exponential filter is τf – the digital filter time constant, Ft1 (Ft2, Ft3, Ft4) interval, within which the temperature reaches the 63.2% from measured value Tmeas.

Reducing τf will lead to a faster device reaction onto discontinuous temperature variations, but also will reduce its protection against interference. Increasing τf value increases the device response rate, while noise is significantly suppressed.

Digital filter characteristics

Figure 3.5 – Filter band characteristic Figure 3.6 – Filter time constant characteristic

3.2.5 Two-Position Regulator (Two-Position Control)

Section titled “3.2.5 Two-Position Regulator (Two-Position Control)”

In the two-position control mode the device works according to one of the two logic types:

Logic №1 (Heater) – used to control a heater operation (tubular electric heaters, for instance), or to produce warning that the current temperature value (Tcurr) is less than the setting value (Tset).

  • The output relay initially closes at values of Tcurr < TsetHS
  • Then opens at Tcurr > Tset + HS
  • And closes again at Tcurr < TsetHS

This effects the two-position control by Tset setting with the HS hysteresis.

Logic №2 (Cooler) – used to control a cooler operation (a fan, for instance), or a warning of exceeding Tset setting value.

  • The output relay initially is ON at values of Tcurr > Tset + HS
  • Then is OFF at Tcurr < Tset
  • And ON again at Tcurr > Tset + HS

Two-position regulator diagram

Figure 3.7 – Diagram of output relay function based on the logic type

Programmable parameters:

  • Tset – temperature setting: SP1 (SP2, SP3, SP4)
  • HS – hysteresis: HS1 (HS2, HS3, HS4)
  • Relay function logic: rt1 (rt2, rt3, rt4)

3.2.6 PID-Controller (Proportional-Plus-Integral-Plus-Derivative Control)

Section titled “3.2.6 PID-Controller (Proportional-Plus-Integral-Plus-Derivative Control)”

On the control relay the “controlling” signal Yi is generated; its action is directed at reducing the Ei deviation.

PID formula

Where:

  • Xp – proportionality band (programmable parameter P)
  • Ei – is the difference between the set Tset and current Tcurr temperature value, or unbalance
  • τd – response speed derivation (programmable parameter “PID-controller derivative constant” - d)
  • ΔEi – difference between two adjacent measurements Ei and Ei-1
  • Δtmeas – difference between two adjacent measurements Tcurr and Tcurr-1
  • τi – integration response time (programmable parameter “PID controller integral constant” i)
  • Σ – derivation cumulative sum

To provide for the efficient PID controller operation it is important that proper values of Xp, τd and τi ratios for the given controlled object be set.

Programmable parameters:

  • [Xp] – P1 (P2, P3, P4)
  • [τd] – d1 (d2, d3, d4)
  • [τi] – i1 (i2, i3, i4)

Proportional regulator is the main where the task of temperature is directly proportional to error. Using only proportional regulator leads to error. The low values of proportional regulator lead to lack of stability and vibration in system but too high lead to low operation.

Proportional regulator

Figure 3.8 – Working diagram of proportional regulator

It’s used for compensation of errors. The temperature will grow to the moment compensation of errors (or diminish by negative error). The minor constituents of integral element influence the regulator job much.

If the value fixed very high it means the system doesn’t recognize it and will work with overshoot.

Integral regulator

Figure 3.9 – Working diagram of integral regulator

It’s used for increasing system performance rating the error change.

The regulator speeding leads to increasing overshoot and as a result is lack of stability the system.

Most cases derivative term is fixed neutral or low value to avoid this lack of stability.

Differential regulator

Figure 3.10 – Working diagram of differential regulator

During the controlling, one of the control methods is selected: “Heater” or “Cooler”.

  • Heater – the output signal value decreases while the controlled temperature grows
  • Cooler – the output signal value increases while the controlled temperature grows

Programmable parameters: rt1 (rt2, rt3, rt4)

3.2.6.6 Action in PID-Regulator Mode with Output Key Element (Pulse-Length Modulation)

Section titled “3.2.6.6 Action in PID-Regulator Mode with Output Key Element (Pulse-Length Modulation)”

Command current from PID regulator (Yi) is transforming to multiple pulses according to the following formula:

D = Tcycle × Yi / 100

Where:

  • D – impulse duration (seconds): L1, L2, L3, L4
  • Tcycle – pulse repetition period (seconds): t1, t2, t3, t4
  • Yi – command current of PID regulator (%)

PLM diagram

Figure 3.11 – Diagram of output relay action in PID regulation mode

Using of interface is described in Appendix A.

Open terminals of the device carry dangerous voltage of up to 250 V. Any connections to the device and its maintenance operations must be performed only on de-energized device and executive units.

Ingress of moisture to the output terminals and the device inside electronic elements is not allowed. The use of the device in aggressive environments containing acids, alkali, oils, etc. is prohibited.

The device connection, adjustment and maintenance must be performed only by authorized personnel that is familiar with this manual.

Recommended maintenance schedule – semiannually.

Maintenance scheduled operations consist of visual observation, during which wiring connection to terminals is checked, frame and casing integrity check for cracking and chipping.

During maintenance operations, the safety precautions listed in chapter 4.1 must be followed.

Prepare cables for connecting the device to sensors, execution mechanisms and peripheral equipment, as well as to the power supply. To provide for the electric connections reliability it is recommended to use cables with copper stranded wires, the ends of which should be carefully cleaned and soldered prior to connecting. The wire core shall be cleared in such way, that its bare ends would not project beyond the terminals after connection to the device. The cable section must not exceed 2.5 mm².

5.1.2 Mounting Instructions Aimed at Electromagnetic Interference Reduction

Section titled “5.1.2 Mounting Instructions Aimed at Electromagnetic Interference Reduction”

When laying the “device-sensor” lines, they should be separated into an individual tract (or several tracts). The tracts shall be placed separately from the power cables, as well as from cables that produce high frequency and pulse interference.

5.1.3 Mounting Instructions Aimed at Reduction of the Power Circuit Interference

Section titled “5.1.3 Mounting Instructions Aimed at Reduction of the Power Circuit Interference”

The device shall be connected to 220V 50Hz circuit feeder that is not connected with supplying power to heavy-duty industrial equipment. It is recommended to install in the peripheral supply line a feed switch providing disconnecting the device from the circuit, as well as 1A fuses.

The device shall be connected in accordance with the diagram on Figure 5.1, observing the listed below sequence:

A) Connect the device to power supply and execution units; B) Connect the “device-sensor” communication lines to the device inputs.

TR-101 devices employ a three-wire diagram for connecting RTDs (resistance temperature detectors). Two wires are connected to one of the RTD outputs, and the third wire is connected to the other RTD output (see Figure 5.1). Such diagram, provided that impedance of all three wires is equal, allows to compensate its impact onto the temperature measurement.

The resistance temperature detectors can be connected to the device under a two-wire diagram as well, but such arrangement does not provide for the connecting wiring impedance compensation which may lead to certain dependence of the device measurement from the wires temperature variation.

5.3.1 Connecting Sensors (RTDs) According to a Two-Wire Diagram

Section titled “5.3.1 Connecting Sensors (RTDs) According to a Two-Wire Diagram”

5.3.1.1 The RTDs (resistance temperature detectors) are connected to the device according to a two-wire diagram in case when a three-wire diagram cannot be used, for example, when TR-101 is installed within units equipped with earlier laid two-wire connection lines.

5.3.1.2 Please, mind that the device readings will depend on the “device-sensor” communication line wires impedance change, that takes place under influence of the outside air temperature. To compensate for the wires parasitic resistance, perform the following:

  1. Before the operation start install a jumper between contacts 23 and 24 ((26 and 27), (29 and 30), (32 and 33)) of the terminal block, and connect the two-wire line immediately to contacts 22 and 23 ((25 and 26), (28 and 29), (31 and 32)).

  2. Then connect a resistor box with accuracy rating not less than 0.05 (P321, for example) to the opposite ends of the “device-sensor” communication line, instead of the thermal element.

  3. On the resistor box, set the value equal to the RTD resistance at temperature of 0 °C (50, 100, 500, 1000 Ohms, depending on the sensor type).

  4. Energize the device and after 20-30 sec, by the digital display readings, define the value of the temperature deviation from 0 °C.

  5. Set the Sh1 (Sh2, Sh3, Sh4) parameter value equal to the temperature deviation value, taken with the opposite sign.

  6. Check the accuracy of the value assigned; to do it, without changing the resistance value on the resistor box, switch the device to the temperature measurement mode, and verify that its reading is equal to 0±1 °C.

  7. De-energize the device, disconnect the communication line from the resistor box and connect it to RTD.

  8. After all these actions, the device is ready for further operation.

TR-101 Connection Diagram

Figure 5.1 – TR-101 Connection Diagram

6.1.1 When the device is powered on, all displays light up for 2 seconds. After that on the digital display the measured temperature for Channel 1 is shown. The device sequentially displays the temperature of the active channels with 4 sec interval.

6.1.2 In case of certain faults presence, the device displays the error code (Table 6.1).

Table 6.1 – Error Codes

FailureDisplayDescription
Parameter errorErPInstead of the faulty parameter TR-101 loads the default value and continues to function normally
EEPROM failureEEPAll relays are open
Sensor short circuitFCCThe corresponding channel relay opens and “sensor failure” and “relay” lights begin to flicker
Sensor disconnectionFOCThe corresponding channel relay opens and “sensor failure” and “relay” lights begin to flicker

The device gives an opportunity to test both all relays at once, or each relay independently; to test, perform the following:

  1. When in parameter edit mode, set the tSt parameter value according to Table 7.1 and press ENTER key; upon that, the display will show OFF message (which means that all relays that are being tested are currently in the normally open (de-energized) state), all LED lights will go off.

  2. Single pressing of ENTER key changes the status of the relays under testing:

    • OFF – the relays are in normally open (de-energized) state
    • On – the relays are in normally closed (energized) state
  3. To switch back to the menu press the MENU key. If no key is pressed during 20 sec the TR-101 device goes into the initial state.

7.1.1 Programmable parameters are set by the user during programming session and are stored in device’s nonvolatile memory.

The complete list of programmable parameter registers is given in Table 7.1.

Table 7.1 – Programmable Parameters

AddressParameterMnemonicMin/MaxFactoryDescription
21Sensor faultAct0/10Loading relay state on sensor fault: 0 – OFF; 1 – ON
AddressParameterMnemonicMin/MaxFactoryDescription
22Indication modedSP0/100 – sequential display (4 sec); 1 – manual view
23PasswordPAS**000/999000000 – password off; any other value activates password prompt
24ResetrSt*0/100 – do not reset; 1 – reset all to factory values
25Relay TestingtSt*0/400 – all relays; 1-4 – test relay 1-4
26VersionvEr*53Device version
AddressParameterMnemonicMin/MaxFactoryDescription
27SwitchingrSA0/200 – OFF; 1 – ON; 2 – Remote Control for Power Relays
28IdentifierrSn1/2471Device number (network address)
29Bit raterSS0/220 – 2400 bps; 1 – 4800 bps; 2 – 9600 bps
30TimingrSL0/9990Delay time of response (×100 µs)
AddressParameterMnemonicMin/MaxFactoryDescription
31Switching channelch10/310 – off; 1 – two-position; 2 – PID; 3 – PID auto tuning
32SettingSP1-50/200 °C100Temperature setting (Tset)
33HysteresisHS10/50 °C1Temperature hysteresis (HS)
34Relayrt10/100 – logic 1 (heater); 1 – logic 2 (cooler)
35Proportional PIDP11/999 °C40PID Proportionality band (Xp)
36Integral PIDi10/999 min130PID integral constant (τi)
37Differential PIDd10/999 min4PID differential constant (τd)
38Periodt160/999 s60Pulse-repetition interval of PLM (Tcycle)
39IntervalL11/999 s1Minimal length of PLM
40Characteristic shiftSh1-50/50 °C0Sensor characteristic shift (0 – disabled)
41Characteristic slopeKU10.50/2.001.00Sensor characteristic slope (Modbus: value ×100)
42Filter bandFb10/50 °C0Digital filter band (0 – disabled)
43Filter timeFt10/60 s2Digital filter time constant (0 – disabled)
44Sensor typeCt10/161See sensor type codes below
AddressParameterMnemonicMin/MaxFactoryDescription
45Switching channelch20/310 – off; 1 – two-position; 2 – PID; 3 – PID auto tuning
46SettingSP2-50/200 °C100Temperature setting (Tset)
47HysteresisHS20/50 °C1Temperature hysteresis (HS)
48Relayrt20/100 – logic 1 (heater); 1 – logic 2 (cooler)
49Proportional PIDP21/999 °C40PID Proportionality band (Xp)
50Integral PIDi20/999 min130PID integral constant (τi)
51Differential PIDd20/999 min4PID differential constant (τd)
52Periodt260/999 s60Pulse-repetition interval of PLM (Tcycle)
53IntervalL21/999 s1Minimal length of PLM
54Characteristic shiftSh2-50/50 °C0Sensor characteristic shift (0 – disabled)
55Characteristic slopeKU20.50/2.001.00Sensor characteristic slope (Modbus: value ×100)
56Filter bandFb20/50 °C0Digital filter band (0 – disabled)
57Filter timeFt20/60 s2Digital filter time constant (0 – disabled)
58Sensor typeCt20/161See sensor type codes below
AddressParameterMnemonicMin/MaxFactoryDescription
59Switching channelch30/310 – off; 1 – two-position; 2 – PID; 3 – PID auto tuning
60SettingSP3-50/200 °C100Temperature setting (Tset)
61HysteresisHS30/50 °C1Temperature hysteresis (HS)
62Relayrt30/100 – logic 1 (heater); 1 – logic 2 (cooler)
63Proportional PIDP31/999 °C40PID Proportionality band (Xp)
64Integral PIDi30/999 min130PID integral constant (τi)
65Differential PIDd30/999 min4PID differential constant (τd)
66Periodt360/999 s60Pulse-repetition interval of PLM (Tcycle)
67IntervalL31/999 s1Minimal length of PLM
68Characteristic shiftSh3-50/50 °C0Sensor characteristic shift (0 – disabled)
69Characteristic slopeKU30.50/2.001.00Sensor characteristic slope (Modbus: value ×100)
70Filter bandFb30/50 °C0Digital filter band (0 – disabled)
71Filter timeFt30/60 s2Digital filter time constant (0 – disabled)
72Sensor typeCt30/161See sensor type codes below
AddressParameterMnemonicMin/MaxFactoryDescription
73Switching channelch40/310 – off; 1 – two-position; 2 – PID; 3 – PID auto tuning
74SettingSP4-50/200 °C100Temperature setting (Tset)
75HysteresisHS40/50 °C1Temperature hysteresis (HS)
76Relayrt40/100 – logic 1 (heater); 1 – logic 2 (cooler)
77Proportional PIDP41/999 °C40PID Proportionality band (Xp)
78Integral PIDi40/999 min130PID integral constant (τi)
79Differential PIDd40/999 min4PID differential constant (τd)
80Periodt460/999 s60Pulse-repetition interval of PLM (Tcycle)
81IntervalL41/999 s1Minimal length of PLM
82Characteristic shiftSh4-50/50 °C0Sensor characteristic shift (0 – disabled)
83Characteristic slopeKU40.50/2.001.00Sensor characteristic slope (Modbus: value ×100)
84Filter bandFb40/50 °C0Digital filter band (0 – disabled)
85Filter timeFt40/60 s2Digital filter time constant (0 – disabled)
86Sensor typeCt40/161See sensor type codes below

Notes:

  • * Parameter available only for reading
  • ** Remote access to computer is forbidden
CodeSensorCodeSensorCodeSensor
0Pt506Ni10012Pt’500
1Pt1007Ni12013Pt’1000
2Pt5008Ni50014Cu’50
3Pt10009Ni100015Cu’100
4Cu5010Pt’5016PTC1000
5Cu10011Pt’100

To view parameters, press MENU key once, the display will show parameter 1 from Table 7.1. Scroll parameters with ▲▼, parameter view – press key ENTER, passage back to menu – press key MENU.

To edit parameters, press and hold MENU key for 7 seconds, at that:

  1. If a password had been set up, enter it. Use ▲▼ keys to change current position, use ENTER key to move to nExt position, use MENU key to confirm the password. Cancel password prompt – if no key has been pressed during 20 sec the TR-101 device returns to the initial state.

  2. If the entered password is correct, the “Setting mode” LED will light (Figure 3.2, item 8), and the display will present the first parameter from Table 7.1.

  3. If the password entered is incorrect, the TR-101 will return to its initial state.

  4. If PAS has been set to “0”, password prompt will not be activated. “Setting mode” LED will light (Figure 3.2, item 8), and the display will present the first parameter from Table 7.1.

Use ▲▼ keys to toggle parameters, use ENTER key to store parameter and return to menu, to return to menu without storing parameter, press MENU key. If no key is pressed during 20 sec the device goes into the initial state.

Method 1: In the parameter edit mode (p. 7.1.3) set rSt parameter to 1 and press ENTER key, after that, the device will perform resetting to default factory set parameters. Password will not be reset in this case.

Method 2: Energize the device while pressing down ▲▼ keys and hold them pressed for over 2 seconds, at that the display will show nAU message; release the keys. De-energize the device. All factory settings including the password have been restored (password is off).

7.2.1 Setting Up Measurement Entry Parameters

Section titled “7.2.1 Setting Up Measurement Entry Parameters”

7.2.1.1 Enter the Ct1 (Ct2, Ct3, Ct4) parameter value in accordance with the sensor type (Table 1, Table 7.1).

7.2.1.2 Measurement Characteristic Adjustment

The measurement adjustment procedure performed by the device is described in paragraph 3.2.3. The device performs measurement adjustment after the necessary values for parameters Sh – sensor measurement characteristic shift and KU – sensor measurement characteristic slope, have been set.

  • Sh parameter can be modified within boundaries from -50 to +50 °C
  • KU parameter can be modified within boundaries from 0.50 to 2.00

7.2.2 Setting Up Digital Filter Parameters

Section titled “7.2.2 Setting Up Digital Filter Parameters”

The digital filter operation is described in paragraph 3.2.4.

The measurement digital filter setting up is performed by specifying two parameters values:

  • Fb – digital filter band
  • Ft – digital filter time constant

The Ft value can be set within limits from 0 to 60 sec; when Ft = 0 filtration by way of exponential smoothing is unavailable.

The Fb value is set within range from 0 to 200 °C; when Fb = 0 the “single interference termination” is off.

7.2.3 Setting Up Relay Control Method Parameters

Section titled “7.2.3 Setting Up Relay Control Method Parameters”

For a specific regulation system, the control method has to be selected by means of setting corresponding values to rt1 (rt2, rt3, rt4) parameter:

  • 0 – logic 1 (heater)
  • 1 – logic 2 (cooler)

The device can function in one of the two modes: the two-position control and PID-control.

The proper mode is set by specifying a proper value for ch1 (ch2, ch3, ch4) parameter:

  • 0 – OFF
  • 1 – two-position control
  • 2 – PID control
  • 3 – Automatic adjustment of PID regulator

The two-position control and PID control operation is described in paragraphs 3.2.5 and 3.2.6.

The two-position controller hysteresis HS (°C) is set under HS1 (HS2, HS3, HS4) parameter, see 3.2.5; the parameter may be modified within range from 0 to +50 °C.

7.2.5.1 General Concept

PID regulator operation is described at p. 3.2.6.

For adjustment of PID regulator needed attend following actions:

  1. Set value of regulator setting SP1 (SP2, SP3, SP4)
  2. Set parameters of pulse-length modulation (PLM) regulation:
    • t – pulse repetition period Tcycle
    • L – minimal pulse length
  3. Set parameters of PID regulation:
    • P – Proportionality band of regulator Xp
    • i – Reaction time of integration τi
    • d – Reaction time of differentiator τd

Option setting t1 (t2, t3, t4) set in seconds from 60 to 999.

Option setting L1 (L2, L3, L4) set in seconds from 1 to 999.

Option setting P1 (P2, P3, P4) set in °C from 1 to 999.

Option setting i1 (i2, i3, i4) set in minutes from 0 to 999. For i = 0 device works as PD regulator.

Option setting d1 (d2, d3, d4) set in minutes from 0 to 999. For d = 0 device works as PI regulator.

For i = 0 and d = 0 device works as P regulator.

Considering that at each individual scheme there are non-periodic External actions of different characters, all coefficients in above shown formulas can change for getting optimal behavior in positive conditions.

Selected parameters for superfine temperature maintenance in steady-state may happen totally unacceptable for suppression transient phenomena for External action or on-exit onto mode.

As well as alternatively.

For another thing in the course of operation controlled plant characteristic regulation can change very much. Like for operational changes and in time.

Usually calculated values require repeated correcting and selection. And changing single parameter involves necessity correcting other.

7.2.5.2 Automatic Adjustment of PID Regulator

This mode designed to autodetection initial approximate values of PID coefficients τi, τd and Xp when operated at concrete scheme.

Automatic tuning is recommended to lead by start and system debugging.

7.2.5.2.1 Enter to program mode (see p. 7.1.3).

7.2.5.2.2 Define SP (Tset) like setting value which in future will be supported by device.

If necessary fix PLM pulses repetition period and minimal PLM pulse length, parameters t1 and L1.

Factory settings are t1 = 60 seconds, L1 = 1 second.

7.2.5.2.3 Define parameter ch1 = 3 (ch2, ch3, ch4).

After pressing key ENTER, at display device will appear blinking caption Pid with number display device for 10 seconds (the time can change depending on fixed time filter Ft1, Ft2, Ft3, Ft4).

On the morrow of time regulator will give continuous output limit and at display device will appear current temperature dotted in low order position “xxx.”.

Whereby output relay of loading will be power on till will not be reach the volume of temperature like SP (Tset).

After switching off loading relay (period I, point B) sometime the temperature mechanically will increase further.

As soon as the control temperature will come down below SP (Tset), process automatic tuning will finish (point G at Figure 7.1) and display device will show continuous lettering Pid.

TR-101 calculates coefficient of PID regulator: band proportionality, characteristic time of integration, characteristic time of differentiator.

After finishing automatic tuning needed press key MENU and switch device to program mode in which is possible to look and correct received coefficients value.

The coefficients were received as a result of “Automatic tuning PID” are not optimal and work for preliminary analysis.

7.2.5.3 PID Regulator Manual Setting

Below mentioned method allows defining approximate generic parameters of regulator.

7.2.5.3.1 Enter to program mode.

7.2.5.3.2 If necessary, fix PLM pulses repetition period and minimal PLM pulse length, parameters t and L.

Factory settings are t = 60 seconds, L = 1 second.

7.2.5.3.3 Fix the value equal to zero for i (τi), d (τd) and P (Xp). Fix SP (Tset) value equal to temperature setting value which will be supported by device in future.

After passage to mode regulation (at the end of 20 seconds the device automatically passes into mode regulation) output relay of loading will be power on till fail to reach regulation temperature (setting limit) Tset (period I, point B at Figure 7.1).

7.2.5.3.4 Take measure t₁ – time from the moment of temperature increase to 10% (point A at Figure 7.1) and to the moment of temperature increase to 63% from the range Tset − Tmax (point B at Figure 7.1).

7.2.5.3.6 Take measure of maximum value overshoot between points B and G (Emax, Figure 7.1).

7.2.5.3.7 Fix the value Xp = 2 × Emax (period II at Figure 7.1).

Make sure that for datum value Xp does not absent achievement of setting value Tset. Otherwise necessary increase the value Xp.

If the value of Xp = 2 × Emax and the difference between steady-state temperature and setting value is too much, then need to diminish Xp.

7.2.5.3.8 Fix the value τi = 2.4 × t₁. Make sure that given value τi not appear temperature vibration around setting value (period III). For decreasing vibration is necessary increase value τi, for increasing delivery speed necessary diminish value τi.

7.2.5.3.9 Fix the value τd equal to [0.1; 0.2; 0.3; 0.4] × τobj.

PID manual tuning

Figure 7.1 – PID regulator manual tuning diagram

8 Service Life, Shelf Life and Manufacturer Warranty

Section titled “8 Service Life, Shelf Life and Manufacturer Warranty”

8.1 The unit service life is 10 years. Upon expiration of the service life you should contact the Manufacturer.

8.2 Shelf life is 3 years.

8.3 Warranty period of the unit operation is 5 years from the date of sale.

During the warranty period the Manufacturer is responsible for free repair of the unit, if the Consumer has complied with the requirements of this Operating Manual.

8.4 Warranty service is performed at the place of purchase or by the Manufacturer of the product.

8.5 Post-warranty service is performed by the Manufacturer at current rates.

8.6 Before sending for repair, the unit should be packed in the original or other packaging excluding mechanical damage.

The device in manufacturer package should be stored in enclosed rooms at -45 to +60 °C and exposed to no more than 80% of relative humidity when there are no fumes in the air that exert a deleterious effect on package and the device material. The Buyer must provide the protection of the device against mechanical damages in transit.


For all questions, please contact the Manufacturer:

“Novatek-Electro” Ltd.

www.novatek-electro.com

59, Mykhailo Boltenko (Admiral Lazarev) str., Odesa, Ukraine, 65007

Tel: +38 (067) 565 37 68 +38 (050) 359 39 11 +38 (063) 301 30 40

VN251029