Appendix C: RPM-416 Software Version History
Ta treść nie jest jeszcze dostępna w Twoim języku.
This appendix provides a complete history of firmware versions for the RPM-416 Data Logger.
Version History
Section titled “Version History”| Version | Date | Description |
|---|---|---|
| v2.6 | 14/03/2025 | Increased transformation factor for channels 4,5,6,7 from 2000 to 9999. Optimized speed for the data acquisition task. |
| v2.5 | 07/02/2025 | Fixed incorrect scaling of channel 11 in the Web-interface. |
| v2.4 | 05/08/2024 | Fixed incorrect user offset for temperature channel 2. Fixed inverted menu for channels 12, 13, 14, 15. |
| v2.3 | 19/01/2024 | Resetting user settings (pressing the UP and DOWN buttons) has been moved. Added a delay after inserting a disk (to stabilize the power supply). |
| v2.2 | 31/05/2023 | Added Ethernet reboot function if Link is out of service for more than 60 seconds. Input event values are normalized (example: 255.0 V, 12.44 A). |
| v2.1 | 02/05/2023 | Fixed the calculation of the power value. |
| v2.0 | 02/05/2023 | Fixed and optimized SPI IO. Added new code for FTP server. Optimized graphical interface. Fixed 1920→1480 points and SRAM 1 and 2 sizes. Optimized memory usage. ARP timer resolution changed from 5 to 1 second. Added Modbus server timeout checking using the timestamp in absolute value. Ethernet DMA has been optimized. Fixed algorithm for saving settings and calibration. Fixed PHY and ETH synchronization. |
| v1.9 | 28/07/2022 | Optimized for the new GD32F107VCT6 MCU. Fixed blocking of flash memory after writing. Fixed reading data via SPI. |
| v1.8 | 27/10/2020 | Data recording loss at maximum speed (1ms) is fixed. |
| v1.7 | 08/04/2019 | Casual reset of the device in mode of sitting is corrected. |
| v1.6 | 21/12/2018 | Formatting of the memory card is corrected. |
| v1.5 | 03/08/2018 | The event counter has been added when the power was applied to the device, as well as the time of recording the last event (registers 23:24 and 25:26). Added the ability to save (load) all settings to a memory card. Changed the scaling of analog channels (10 and 11), now it is necessary to set the input and output range of values. The FatFs file system library has been updated to version 13b. Improved the password entry screen. Corrected the error #5 when recording events in the ring mode. Optimized the SPI frequency to support slower cards. Time synchronization with PC has been optimized. Optimized the display of measured values on the front panel. Optimized the algorithm for determining the Ethernet cable connection. Corrected a critical error that caused the device to reboot. General system performance improvements. |
| v1.4 | 11/04/2017 | Line voltage measurement has been added (channel 19). Corrected the scaling of analog signals (channels 10 and 11). Improved the time correction to 99.9 s per day. Fixed hang-up of Ethernet DMA when pinging the device in large packets of 65,500 bytes. |
| v1.3 | 21/07/2016 | Added scaling of analog signals for channels 10 and 11. Electric power meters have been added. Counters of discrete signals have been added. Added the ability to change the password from the front panel (Modbus, Ftp, Http). Modbus network identifier has been added. Corrected the removal of old files in the write mode by the ring. |
| v1.2 | 28/07/2015 | Added measurements: harmonics of voltage and current, peak values of voltages and current. Added the support for expansion modules. Added the ability to connect to the server Overvis. Completely rewritten protocols: Modbus, Ftp and Http. Improved the correction of the real-time clock. |
| v1.1 | 12/11/2014 | The folder names have been corrected when working with FTP. Minor corrections. |
| v1.0 | 30/08/2014 | The first version of the software. |
Checking Your Firmware Version
Section titled “Checking Your Firmware Version”To check the current firmware version of your RPM-416:
- Navigate to Menu → Device version on the front panel display
- Or read Modbus register 1 (firmware version)
- Or check the Device version section in the Web-interface
Firmware Updates