Appendix B: UBZ Operation for Motor Control with Winding Changeover When Star-to-Delta Starting
Цей контент ще не доступний вашою мовою.
For operation of UBZ-304 for motor with windings changeover when star-to-delta starting, connect the device according to Figure B.1.

Figure B.1 – Diagram for UBZ enabling for the motor operation with star-delta switching over and the motor insulation control
Components
Section titled “Components”- K1 – Starter of motor enabling
- K2 – Star starter of motor winding enabling
- K3 – Delta starter of motor winding enabling
- Q1 – Automatic breaker
Motor Control Methods
Section titled “Motor Control Methods”When UBZ is in the star-delta mode, it is allowed to perform motor control in the following ways:
- External automatic starter control – Motor disabling/enabling using the external automatic starter (actuator) at the same time with the de-energizing/energizing the UBZ device
- Front panel control – Motor control on the front panel of UBZ
- Remote control – Motor control via RS-232/RS-485 interface
Related Settings
Section titled “Related Settings”The functional relay mode must be set to “St->D” (star-delta) for this operation mode. See the Functional relay operation section in the main manual for configuration details.
The following parameters are relevant for star-delta starting:
| Parameter | Description |
|---|---|
| Relay F mode | Set to “St->D” for star-delta operation |
| Relay F time | Time delay before switching from star to delta |
| Delay RP RF | Delay between load relay off and functional relay activation |
For the complete list of programmable parameters, see the main manual.