Appendix G: Updating Firmware
Цей контент ще не доступний вашою мовою.
General Information
Section titled “General Information”To upgrade the integrated software, EM-486 uses files EM486FW1.FUS, EM486FW2.FUS or EM486FW3.FUS from folder UPGRADES located on SD memory card, formatted in the FAT or FAT32 format. Updating these files may be held in a special update mode of firmware.
Transmitting the EM-486 Updating Files
Section titled “Transmitting the EM-486 Updating Files”To transfer the update files, it is possible in two ways:
- Record files to SD card on a personal computer or other external device and put the card into the EM-486, then enter the upgrade mode of the firmware, as shown in the table below;
- If updating via the WEB interface is allowed in the parameter’s settings, on the “Other” tab (see section 5.3.3 of the manual) - go to the “Files” tab, select the transition to “Firmware update”, select the file and click the “Upload file”. The file will be written to the “UPGRADES” folder named “EM486FW2.FUS”. Then press the “Program” button. Wait for the update (3-4 minutes).
Firmware Updating Mode
Section titled “Firmware Updating Mode”The device can be set in mode of firmware updating after power supply and restart. The setting in that mode is made automatically (at updating via WEB-interface or at update failure) or manually (at the button “R” being pressed during a startup).
Entering the Mode of Software Updating
Section titled “Entering the Mode of Software Updating”| № | Step | Button “R” | Display | Time | Remark |
|---|---|---|---|---|---|
| 1 | Initialization | Pressed | 0.5 s | To cancel the updating, release the button “R” at these steps | |
| 2 | Stand-by | Pressed | 1 s | ||
| 3 | Notification about entering in mode of updating | Pressed | Entering upgrade mode | 5 s | |
| 4 | Offer to enter the mode of updating | Pressed | To enter upgrade mode release button | 2 s | To enter the mode of software updating, release the button “R” at this step |
| 5 | Protection against incidental pressing | Pressed | – | – | Holding the button pressed will cancel the firmware updating |
Selection of Updating File
Section titled “Selection of Updating File”After manual entering in mode of updating, select the file of updating. To cancel the updating, cut off the power supply of EM-486 or wait until automatic completion of updating mode.
| № | Step | Button “R” | Display | Time | Remark |
|---|---|---|---|---|---|
| 1 | Finding the available files | Searching for upgrade files… | (depends on the found files) | ||
| 3 | Notification about entering in mode of updating | released | Name and version of updating file | 5 s | To select a file, press and release the button “R” at this step |
| 4 | Offering all files of updating | released | – | (depends on the found files) | Repeat the step 3 for each file |
| 6 | Repeated offer | released | – | (depends on time of step 4) | Repeat the steps 3–4 for 3 times |
| 7 | Protection against incidental entering in the mode of updating | released | – | – | The file cancelation cause the escape from the mode of firmware updating |
Updating of Integrated Firmware
Section titled “Updating of Integrated Firmware”At automatic entering into the mode of firmware updating or at manual selection of file, the updating is made from the file.
| № | Step | Button “R” | Display | Time | Remark |
|---|---|---|---|---|---|
| 1 | Start of updating | – | Upgrading Firmware | 2–10 s | |
| 2 | Updating the integrated software | – | (performance line shows the process of updating) | (depends on the file of updating) | Time until the end of process of updating is shown on the display |
| 3 | Updating is successfully completed | – | Firmware upgrade success | 5 s | |
| 4 | Startup of firmware | – | – | – |
Error Codes
Section titled “Error Codes”The errors detected during the updating process are shown on the display.
Codes of Warning in Software Updating Mode
Section titled “Codes of Warning in Software Updating Mode”| Code | Warning | Actions | Remarks |
|---|---|---|---|
| 2 | Integrated firmware cannot be started | Initialization of mode of emergency updating: Auto start of updating from the selected file or from the first available file (if any) | The warning is shown at selection of firmware updating in WEB-interface or as a result of other error and is automatically corrected with the help of available files of software updating |
| 3 | Error while current process of firmware updating | Similar to №2, but the file with an error has less priority | The error is automatically corrected with available files of updating |
| 4 | The files of updating are not available | Escape from the mode of updating, start of available integrated firmware | The device can continue operation but for reprogramming the file of updating should be loaded in the folder “UPGRADES” on the device SD memory card |
| 5 | Emergency mode – firmware cannot be started | Waiting for manual restart of device or restart automatically in 1 hour | The error is a result of three-time entering in emergency mode as a result of other errors. The correct file of firmware updating should be loaded in the folder “UPGRADES” on the SD memory card. If the error is repeated, contact the manufacturer |
| 6 | Emergency mode – error during the current firmware updating | Waiting for manual restart of device or restart automatically in 1 hour | The error is a result of three-time entering in emergency mode as a result of other errors. The correct file of firmware updating should be loaded in the folder “UPGRADES” on the SD memory card. If the error is repeated, contact the manufacturer |
| 7 | Unrecoverable error – no available files of updating, the integrated firmware cannot be started | Waiting for manual restart of device or restart automatically in 1 hour | The error is a result of three-time entering in emergency mode as a result of other errors. The correct file of firmware updating should be loaded in the folder “UPGRADES” on the SD memory card. If the error is repeated, contact the manufacturer |