Перейти до вмісту

Appendix D: Modbus Registers

Цей контент ще не доступний вашою мовою.

Format of Parameters Presentation in MODBUS Registers

Section titled “Format of Parameters Presentation in MODBUS Registers”
ParameterRange of ValuesDescriptionNumber of Occupied Registers
Number0 – 65535Whole number (16 bit) in standard range of MODBUS register values1
Number-32768 – +32767Whole number (16 bit) in additional arithmetic1
Number0 – 4294967295 in two registers, upper part – the first oneWhole number, which value can exceed the limit for MODBUS register (65535)2
Number-2147483648 – +2147483647 in two registers, the upper part is the firstAn integer (32 bits) in complement arithmetic2
Line of symbolsIn each register, a number from 0 to 255 – ASCII-code of symbol or 0 (the end of line)A set of values every of which is equal to symbol code in ASCII encoding. If the line is shorter than the maximal length then after the last symbol there should be code 0Max. length of line for the parameter
IP-address (IP-mask)In every register – one byte (0 – 255)Set of four bytes of address IPv4, from left to right4
MAC-addressIn every register – one byte (0 – 255)Set of six bytes of address MAC-48, from left to right6

Parameter Groups Available via MODBUS Protocol

Section titled “Parameter Groups Available via MODBUS Protocol”
GroupDescriptionAccessAddress
Device descriptionParameters are listed in Device Describing Parameters tableAny mode, only reading0 – 3
Current modeParameters are listed in Current Mode Parameters table. Password entry is available in any mode, command entry - only in setup mode (after password entry)Depending on the mode100 – 120
Current statusParameters are listed in Current Status Parameters tableAny mode, only reading121 – 295, 900 – 944, 5000 – 5249
Changeable settingsThe parameters listed in Settings Parameters table that can be changed and activatedOnly in mode of setting, for reading or writing300 – 829, 5250 – 5499
Active settingsThe settings being used by the device at the momentIn any mode, only reading2300 – 2829, 5500 – 5749
Saved settingsThe set is saved regardless the power of the EM-486 and is used at starting of the deviceOnly in mode of setting, only reading3300 – 3829, 5750 – 5999
Clock settingSee Clock Setting Parameters tableOnly in clock setting mode, for reading or writing34817 – 34825
ParameterDescriptionAddress
Type of deviceThe code defining the instrument MODBUS at the manufacturer (15 – EM-486)0
Program versionProgram version of integrated firmware of the device1
Control codeCRC32 of the device program integrated firmware2 – 3
ParameterRange of ValuesInitial ValueDescriptionAddress
Password enterLine of symbols0At entering the actual password, the client receives the appropriate access (see the registers 710-749). At entering the empty line, the rights of client are reset to level at the moment of connection100 – 119
Command of control0 – 40959, Writing in mode of setting0See Control Commands table120
ValueCommandDescription
0No activity-
1RestartRestart of the device
2SaveSave the changes of settings via MODBUS
3ApplyApply the settings without restart (It is only available for MODBUS, relays, transducers and user parameters)
4Save and applySimilarly to commands 2 and 3
6ExportRead the saved settings and write them to a file on the memory card (see Appendix E)
7ImportRead settings from a file on a memory card and save them
9CancelTo read the saved settings
21Deactivate relay K1Switch the relay K1 in normal state until the next command on relay or until reset of the device
22Deactivate relay K2See command 21
23Deactivate relay K3See command 21
29Deactivate all relaysSwitch all relays in normal state until the next command on relays or until reset of the device
31Activate relay K1Switch relay K1 in active state until the next command on relay or until reset of the device
32Activate relay K2See command 31
33Activate relay K3See command 31
39Activate all relaysSwitch all relays in active state until the next command on relay or until reset of the device
41Control of relay K1Switch relay K1 to automatic control (normal state before the events which are programmed for switching this relay) until the next command on relay or until reset of the device
42Control of relay K2See command 41
43Control of relay K3See command 41
49Control of all relaysSwitch all relays to automatic control (normal state before the events which are programmed for switching these relays) until the next command on relay or until reset of the device
51Apply for MODBUSApply the settings via MODBUS and RS-485
54Apply for inputApply the settings at inputs sensors
55Apply for outputApply the settings at the output of loading relays
59Apply for userApply the settings for the user area of registers
61Reset saved pulse counter at input 1Before sending this command, you should open the access to change the saved counters (see command 13785)
62Reset saved pulse counter at input 2See 61
63Reset saved pulse counter at input 3See 61
64Reset saved pulse counter at input 4See 61
81Synchronize clock with NTC server-
82Obtain account balance from GSM operator-
161Test SMSSend a SMS test to the number of the main subscriber
10637Back to Factory SettingsReset the settings to the factory settings
13785Start changing the stored pulse countersIt should be sent every time before usage of commands 61 – 64
35381Start setting the clockIt allows access to the registers of clock setting 61 – 64
35431Cancel setting the clockIt allows access to the registers of clock setting
40959Clear the internal memory of the tasksTo erase the program for logic of actions (when the memory card is inserted, it will automatically read again)
ParameterDescriptionAddress
Mode (see details for reg. 122)0: User’s mode; 1: Mode of setting121
Tabs of accessSee Access Flags table below122
Time, minNumber of minutes since the moment of start-up123 – 124
Number of MODBUS TCP clientsNumber of occupied connections of MODBUS TCP125
Limit of MODBUS TCP clientsTotal number of possible connections via MODBUS TCP126
Load of RS-485, inquiries/sNumber of inquires sent via RS-485 per second127
Working load of RS-485, inquiries/sNumber of replies without errors via RS-485 per second128
Load of RS-485 per second, %Loading of RS-485 for the last second, with taking into account set rate of RS-485 and time of inactivity129
Load of RS-485 per minute, %Loading of RS-485 for the last minute130
Load of RS-485 per 5 minutes, %Loading of RS-485 for the last five minutes131
Load of MODBUS TCP, inquiries/sNumber of inquiries received from the clients via MODBUS TCP per second132
Useful load of MODBUS TCP, inquiries/sNumber of replies without errors being sent to the clients via MODBUS TCP per second133
Load of GSM, kB/sWireless channel load channel with GSM being switched on134
Load of Ethernet, ×100 kB/sLoading of wire channel with Ethernet being switched on135
Max. clients of MODBUS TCPMaximal number of simultaneously connected clients via MODBUS TCP – from the moment of start up136
Max. load of MODBUS TCP, inquiries/sMaximal number of inquiries received per second from the clients via MODBUS TCP – from the moment of start up137
Max. load of RS-485, %Maximal loading of RS-485 for 5 minutes – from the moment of start up138
Max. load of GSM, kB/sMaximal loading of GPRS – from the moment of start up139
Current IP-address of EthernetIP-address, by which the device is available in Ethernet network140 – 143
Current MAC-address of EthernetMAC-address, by which the device is detected in Ethernet network144 – 149
State of universal input 1The readings of gauge connected to input 1, depending on the type of gauge (see register 580): for the gauges with analogue output – the value of gauge output in mV or in µA (depending on the type of gauge); for discrete breakers – 0 at open contacts, 1 at closed contacts; for temperature gauges – the measured value of temperature, 32767 – at gauge cut off, -32768 – at gauge short circuit150
The effective value of input 1 stateThe gauge readings at the input 1 given as to the user scale, in accordance to the settings (see registers 766 – 767)151
State of universal input 2The readings of the gauge connected to input 2152
The effective value of input 2 stateThe gauge readings at the input 2 given as to the user scale, in accordance to the settings153
State of universal input 3The readings of the gauge connected to input 3154
The effective value of input 3 stateThe gauge readings at the input 3 given as to the user scale, in accordance to the settings155
State of universal input 4The readings of the gauge connected to input 4156
The effective value of input 4 stateThe gauge readings at the input 4 given as to the user scale, in accordance to the settings157
State of relay output 10 – relay off, 1 – relay on160
State of relay output 20 – relay off, 1 – relay on161
State of relay output 30 – relay off, 1 – relay on162
Time before connection to remote server, s0: there is a connection to server of data accumulation; 1: The connection is being made to the server of data accumulation; 2 – 65534: number of seconds before the repeated connection; 65535: connection to server is not used165
Number of planned restartsNumber of restarts in accordance to the user setting – for total operational time of the device166
Number of critical errorsNumber of noted errors (failures) causing the restart of the device – for total operational time of the device167
Operation time of device, minNumber of minutes of device operation – for total operational time of the device168 – 169
Current time, sNumber of seconds since 1st of January of specified year (see reg. 172)170 – 171
Year of time countYear, since 1st of January which is taken for time count172
Time zone, minTime zone, for the time count, number of minutes with sign as to UTC+00173
Temperature, °CDevice internal temperature174
Power voltage, mVBus voltage 12 V (voltage at the output of the internal power source or at inlet of backup power, depending on which the voltage is higher)175
Time before connection to the first remote server MODBUS TCP0 – there is a connection to remote server; 1 – the connection is being made to remote server; 2 – 65534: number of seconds before the repeated connection; 65535: connection to server is not used176
Interface connection to the first remote server MODBUS TCP0 – there is no connection; 1 – there is a connection by Ethernet; 2 – there is a connection to GPRS177
Adding daylight saving time, minCurrent adding daylight saving time178
Relay control stateSee Relay Control State Flags table179
Pulse counter at input 1Number of pulses at input 1 after starting200 – 201
Pulse counter at input 2Number of pulses at input 2 after starting202 – 203
Pulse counter at input 3Number of pulses at input 3 after starting204 – 205
Pulse counter at input 4Number of pulses at input 4 after starting206 – 207
Year (current time)Current year210
Month (current time)Current month211
Day of the month (current time)Current day of the month212
Hour (current time)Current hour213
Minute (current time)Current minute214
Second (current time)Current second215
Day of week (current time)Current day of week (1 – Monday)216
Month (winter time)Current month, excluding summer time217
Day of the month (winter time)Current day of the month, excluding summer time218
Hour (winter time)Current hour, excluding summer time219
Filter of the value of input 1Last change of register 150 with a delay of 5 seconds220
Filter of the reduced value of input 1Last change of register 151 with a delay of 5 seconds221
Filter of the value of input 2Last change of register 152 with a delay of 5 seconds222
Filter of the reduced value of input 2Last change of register 153 with a delay of 5 seconds223
Filter of the value of input 3Last change of register 154 with a delay of 5 seconds224
Filter of the reduced value of input 3Last change of register 155 with a delay of 5 seconds225
Filter of the value of input 4Last change of register 156 with a delay of 5 seconds226
Filter of the reduced value of input 4Last change of register 157 with a delay of 5 seconds227
The time of day, sNumber of seconds from midnight of the current day230 – 231
The time of sunrise, s0 – 86399: Number of seconds from midnight to sunrise; 86400: Sunrise is not observed in this day232 – 233
The time of sunset, s-1: Sunset is not observed in this day; 0 – 86399: Number of seconds from midnight to sunset234 – 235
Time of day, msNumber of ms from midnight of the current day236 – 237
Memory card occupancy, 0.01%10000 – memory card is missing or full238
Estimated time spent on 1% of the memory card, days0 – less than one day; 1 – 9999 – days for 1% of the memory card capacity; 10000 – more than 10000 days; 65535 – unknown239
Time before connecting to the second remote MODBUS TCP server, s0 – a connection to a remote server has been established; 1 – connecting to a remote server; 2 – 65534: number of seconds before reconnecting; 65535: Connection to MODBUS TCP server is not in use240
Interface for connecting to a second remote MODBUS TCP server0 – connection not established; 1 – an Ethernet connection is established; 2 – the GPRS connection is established241
Connection time to the third remote MODBUS TCP server, s0 – a connection to a remote server has been established; 1 – connecting to a remote server; 2 – 65534: number of seconds before reconnecting; 65535: Connection to MODBUS TCP server is not in use242
Connection interface to a third remote MODBUS TCP server0 – connection not established; 1 – an Ethernet connection is established; 2 – the GPRS connection is established243
Stored pulse counter at input 1The number of pulses at input 1 during the operation of the memory card250 – 251
Stored pulse counter at input 2The number of pulses at input 2 during the operation of the memory card252 – 253
Stored pulse counter at input 3The number of pulses at input 3 during the operation of the memory card254 – 255
Stored pulse counter at input 4The number of pulses at input 4 during the operation of the memory card256 – 257
The stored pulse counter at input 1 (battery)Number of pulses at input 1 during operation of built-in battery of the clock270 – 271
The stored pulse counter at input 2 (battery)Number of pulses at input 2 during operation of built-in battery of the clock272 – 273
The stored pulse counter at input 3 (battery)Number of pulses at input 3 during operation of built-in battery of the clock274 – 275
The stored pulse counter at input 4 (battery)Number of pulses at input 4 during operation of built-in battery of the clock276 – 277
Operating time of the relay 1, sec (battery)Time in seconds during which the relay 1 is turned on (during operation of the built-in battery)280 – 281
Operating time of the relay 2, sec (battery)Time in seconds during which the relay 2 is turned on (during operation of the built-in battery)282 – 283
Operating time of the relay 3, sec (battery)Time in seconds during which the relay 3 is turned on (during operation of the built-in battery)284 – 285
Switching-off counter of relay 1 (battery)Switching-off number of relay 1 (during operation of the battery)290 – 291
Switching-off counter of relay 2 (battery)Switching-off number of relay 2 (during operation of the battery)292 – 293
Switching-off counter of relay 3 (battery)Switching-off number of relay 3 (during operation of the battery)294 – 295
Current IP-address of GSMIP-address obtained from GSM provider900 – 903
GSM signal level, %Signal level and quality of radio communication with GSM provider915
The type of battery connectionType of hardware connection of the built-in battery power (battery for real time clock): 0 – the battery powers the clock in the central controller - memory of statistics (registers 270 – 299, 5240 – 5249); 1 – the battery powers the clock in GSM module, the memory of statistics is reset to zero when power is off927
SIM card account statusThe account status received for the last USSD query (sent automatically once a day); the first number in the operator’s response is taken as an account. -2147483648 – account status is unknown932 – 933
Time for receiving the SIM card account status valueNumber of seconds since January 1 of specified year (see reg. 172). 0 – account status was not received934 – 935
Memory card capacity, kB0 - no card or unformatted in FAT / FAT32941 – 942
The amount of data that has not been written to the memory card since the start, bytes0 - there was no data record losses; 4294967295 - more than 4 GB losses943 – 944
User parameters of statusUser parameters of status after starting take a value of 0. They can be used for storage and transmission to the server of tasks of values to be measured and calculated in the files, and noted events5000 – 5239
User parameters of statistics (battery)They store the value for the operating time of the built-in battery for the clock. They can be used in the task files for statistics gathering or saving state5240 – 5249
BitDescription
0Possibility for the connected client to obtain permission (using a password) for requests for the functions of reading devices via RS-485: 0 - permission cannot be obtained; 1 - permission can be obtained by password
1Allowing the connected client to request functions of reading devices via RS-485: 0 - no permission; 1 - permission is available
2The ability for the connected client to obtain permission (using a password) to request recording functions and control devices via RS-485: 0 - permission cannot be obtained; 1 - permission can be obtained by password
3Allowing the connected client to request recording and device control functions via RS-485: 0 - no permission; 1 - permission is available
4The ability for the connected client to obtain permission (using a password) to access the EM-486 registers, except for the version registers, password, mode and access flags: 0 - permission cannot be obtained; 1 - permission can be obtained by password
5The ability for the connected client to obtain permission (using a password) to access the EM-486 registers, except for the version registers, password, mode and access flags: 0 - permission cannot be obtained; 1 - permission can be obtained by password
7Permission to the connected client to configure EM-486 (similar to register 121): 0 - no permission; 1 - permission is available
9Client has an authority for connection (always is read as «1» after connection)
12Allowing the connected client to set the clock: 0 - no permission; 1 - permission is available
BitDescription
0Indication of relay K1 ON (independent of reg. 575)
1Indication of relay K2 ON (independent of reg. 576)
2Indication of relay K3 ON (independent of reg. 577)
40 - Relay K1 in automatic mode (bit 12); 1 - Relay K1 in manual mode (depends on bit 8)
50 - Relay K2 in automatic mode (bit 13); 1 - Relay K2 in manual mode (depends on bit 9)
60 - Relay K3 in automatic mode (bit 14); 1 - Relay K3 in manual mode (depends on bit 10)
8Manual command for K1 relay to switch on
9Manual command for K2 relay to switch on
10Manual command for K3 relay to switch on
12Automatic command for K1 relay to switch on
13Automatic command for K2 relay to switch on
14Automatic command for K3 relay to switch on
ParameterRange of ValuesFactory ValueDescriptionAddress
Static IP-addressIP-address192.168.0.111If dynamic addressing is disabled or not available, the value of the IP address in the Ethernet300 – 303
Sub network maskIP-mask255.255.255.0It is used only with a static IP-address304 – 307
GatewayIP-address192.168.0.1It is used only with a static IP-address, or as IP filter for DHCP-server308 – 311
Switch on the dynamic addressing with a help of DHCP0 – 110: preset IP-address, mask and gateway is used for addressing in Ethernet. 1: If the DHCP server is available in the network, then the IP address, mask and gateway are received from the server312
Switch on the filter of IP-address of DHCP-server0 – 10Used if dynamic addressing is enabled. 0: device receives addressing data from the first DHCP-server to respond; 1: device receives addressing data only from DHCP-server with IP-address of the gateway313
Switch on the use of server DNS of gateway0 – 11It is used if DHCP is not available (switched off). 0: DNS of gateway is not used; 1: To determine the IP addresses of other servers, if they are specified by host names314
IP-address of the first DNS serverIP-address8.8.8.8Used if DHCP is not available (disabled). 0.0.0.0 - not used315 – 318
Second DNS server IP addressIP-address0.0.0.0It is used if DHCP is not available (switched off). 0.0.0.0 – not used319 – 322
Enable MAC address override0 – 100: unique value for every device, stored in the memory shall be used as a MAC-address; 1: manually set MAC-address is used323
Manually specified MAC-address of EthernetMAC-addressUnique for each deviceUsed if manually set MAC-address is enabled for the authentication of device in the Ethernet network Ethernet324 – 329
ParameterRange of ValuesFactory ValueDescriptionAddress
Pin code of SIM-card0 – 65535655350 – 9999: this code is used for the SIM card if it demands the PIN code. Other values: the code isn’t used, SIM card and GSM are unavailable if the card demand a code330
Switch on the automatic definition of APN and USSD query of GSM operator0 – 110: device makes GPRS connection by manually set APN parameters, to receive the status of the account, a USSD query is sent manually; 1: APN and USSD account status query are automatically determined for the operator according to ICCID code of SIM card331
Activate GPRS in roaming0 – 110: GPRS is blocked in roaming; 1: GPRS may be used in roaming332
Activate SMS messages sending in roaming0 – 100: SMS messages cannot be sent (but can be received) in roaming; 1: SMS messages can be received and sent in roaming333
MODBUS TCP connection port via GSM0 – 655350It is used for external connection to the device via GSM with static IP, for exchange using MODBUS TCP protocol. 0 – It is disabled334
USSD query to receive an accountLine of symbols-It is provided by GSM service provider; up to 12 characters. There cannot be any spaces in a string340 – 351
APN log-in of GPRS serviceLine of symbols-Specified by provider of GSM service. Up to 40 symbols352 – 391
APN password of GPRS serviceLine of symbols-Specified by provider of GSM service. Up to 24 symbols392 – 415
APN address of hostLine of symbols-Specified by provider of GSM service. Up to 34 symbols. In line there should not be any spaces416 – 449
ParameterRange of ValuesFactory ValueDescriptionAddress
Connection port via MODBUS TCP1 – 65535502Used at external connection to the device for exchange via MODBUS TCP protocol450
Disable inactive clients0 – 110 - MODBUS TCP connection is supported regardless of the time between requests from the client; 1 - disconnect clients that have not received requests for longer than a specified time451
Max. reply waiting time, s0 – 60000090Used if disable inactive clients is selected452 – 453
Enable the order for the last made connection via MODBUS TCP0 – 100: connection via MODBUS TCP is supported regardless of connection holding time; 1: If all connections via MODBUS TCP are used, a new client inquiring for connection can be connected instead of the last connected client, if the time of connection holding on is more than the specified time454
Max. time of last connection holding via MODBUS TCP, ms0 – 60000060000Used if the order for the last connection via MODBUS TCP is enabled455 – 456
ParameterRange of ValuesFactory ValueDescriptionAddress
Native MODBUS-identifier of the device0 – 2471110: device forwards all MODBUS TCP requests into the MODBUS network, device registers via MODBUS TCP are unavailable; 1–247: devices respond to MODBUS TCP requests bearing the given MODBUS-identifier without forwarding them to the MODBUS network457
Bit rate via RS-485, bit/sec75 – 9216009600Used in case of data exchange between the devices via RS-485, the same value for the devices on the same bus-bar458 – 459
Activate selection of byte format when transmitting via RS-4850 – 11Used in case of data exchange between the devices via RS-485, the same value for all devices on the same bus-bar. 0: unused, byte is completed with 2 stop bits; 1: Byte format is selected in register 461460
Byte format when transmitting via RS-4850 – 55Is used for exchange with devices via RS-485 only if byte format selection is activated. The value for devices on the same bus-bar. 0: even (“EVEN”) – 1 parity bit and 1 stop bit; 1: odd (“ODD”) – 1 parity bit and 1 stop bit; 2: «0» (“SPACE”) – 1 zero bit and 1 stop bit; 3: «1» (“MARK”) – 1 device bit and 1 stop bit (similar to mode with two stop-bits); 4: “ABSENT” – no parity bit, 1 stop bit; 5: “AUTO-STOP” – no parity bit, 2 stop bits in the outcoming bytes, 1 stop bit in the incoming bytes; in such a case, devices with one and two stop bits may be connected simultaneously461
Response time from MODBUS RTU, ms0 – 60000200Used in case of data transfer via RS-485 in RTU mode. Waiting for a response is terminated if the first byte of the response has not been received within the given time after sending the request. The response is always expected longer than time of silence between frames (time of silence depends on the bit rate and shall be equal to the time required for transmitting 3.5 bytes, or 1.75 msec for bit rate over 19200 bits/sec)462
Enable ASCII exchange via RS-4850 – 10Exchange mode via RS-485, the same value for all devices on the same bus-bar. 0: RTU exchange mode (format: 1start bit, 8 data bits, 2 stop-bits, parity bit, and stop bit or only 1 stop bit – total from 10 to11 bits); 1: ASCII exchange mode (format: 1start bit, 7data bits, 2 stop-bits or parity bit or stop bit – total 10 bits). The non-standard byte forms 4 (register 461, values 4 and 5) are not accessible; format 3 (2 stop bits) is used instead463
Response time for subsequent MODBUS ASCII character, ms0 – 600001000Used in case of data transfer via RS-485 in ASCII mode. Waiting for a response is terminated if the subsequent byte of the response has not been received within the given time, as indicated for the reception of response. Waiting time shall not be less than time required for transmission of a single character (depending on the bit rate)464
ParameterRange of ValuesFactory ValueDescriptionAddress
Mode of connection to the server for data accumulation0 – 410: connection to server is not used; 1: the device makes and holds the connection to the server via the specified connection port (port on the North side); 2: passive mode, waiting for a connection from the server through the specified server connection port (port on the EM-486 side); 3: similar 1, but only via Ethernet; 4: similar 1, but only via GPRS465
Server connection port0 – 6553520502Inquiry port to which is addressed a side making a connection between a device and a server (see reg. 465)466
Time of waiting for a reply from the server, sec0 – 36001200: the server silence time is not limited; 1–3600: max. time of server silence after which the connection will be broken and must be remade again467
Time of waiting before the second connection to the server, s0 – 3000015Connection to the server of data accumulating (used in except the mode «2»). After the connection with the server is lost, the reconnection will be made after a specified waiting time (after starting the device, the first connection is made after a fixed time - 5 s)468
Enable the server address by a text line0 – 11Used in connection to accumulating server (in except the mode «2»). 0: the connection is made to the server with a fixed IP-address set in the registers 470 – 473; 1: connection is made to the server with a name set in the registers 474 – 509469
Data collection server IP addressIP-address0.0.0.0Used in connection to the server (in except the mode «2») if the setting of server address is not activated by a text line. IP-address of remote server which supports the connection470 – 473
Data collection server addressSymbols linemodbus.overvis.comUsed in connection to the server (in except the mode «2») if the setting of server address is activated by a text line. Remote server address which supports the connection. As an address there can be a line with length up to 36 symbols. There should be no spaces in the line474 – 509
ParameterRange of ValuesFactory ValueDescriptionAddress
Specified password for access to the mode of settingLine of symbols11111Used for access to the mode of setting EM-486. As a password there can be used a line with length from 5 to 10 symbols. There should be no spaces in the line510 – 519
Specified password for writing access via incoming SMSLine of symbolsgapUsed for verification of incoming SMS with inquiry for writing of alarm confirmation. As a password there can be used a line with length from 3 to 10 symbols. There should be no spaces in the line530 – 539
Specified password for reading access via incoming SMSLine of symbolsgapUsed for verification of incoming SMS with inquiry for reading of alarm confirmation. As a password there can be used a line with length from 3 to 10 symbols. There should be no spaces in the line540 – 549
Specified password for writing access via MODBUS TCP in devices (in except the EM-486)Line of symbols-Used for access to the devices connected to EM-486, for inquiry of functions of writing or control, that can change the state of these devices. As a password there can be used a line with length up to 10 symbols. There should be no spaces in the line550 – 559
Specified password for reading access via MODBUSLine of symbols-Used for access to the devices connected to EM-486, for inquiry of functions of reading or for access to registers of EM-486 except for registers of version, password, mode and tags. As a password there can be used a line with length up to 10 symbols. There should be no spaces in the line560 – 569
Enable the protection mode against writing via SMS0 – 100: protection against writing is regulated with help of other parameters (password); 1: blocking of inquiries via SMS for function of writing570
Enable the protection mode against reading via SMS0 – 100: protection against reading is regulated with help of other parameters (password); 1: blocking of inquiries via SMS for function of reading571
Enable the protection mode against writing via MODBUS TCP0 – 100: protection against writing is regulated with help of other parameters (password) or deactivated; 1: blocking of any function inquiries except for functions of MODBUS 1, 2, 3, 4, 7, 17, 20572
Enable the protection mode against reading via MODBUS TCP0 – 100: protection against reading is regulated with help of other parameters (password) or deactivated; 1: blocking of inquiries for MODBUS functions 1, 2, 3, 4, 7, 17, 20, except for reading of functions of three registers of version, mode and tabs573
ParameterRange of ValuesFactory ValueDescriptionAddress
Normal state of relay K10 – 100 – in normal state the relay is OFF; 1 – in normal state the relay is ON, a command for switching on the relay, deactivates it575
Normal state of relay K20 – 100 – in normal state the relay is OFF; 1 – in normal state the relay is ON, a command for switching on the relay, deactivates it576
Normal state of relay K30 – 100 – in normal state the relay is OFF; 1 – in normal state the relay is ON, a command for switching on the relay, deactivates it577
ParameterRange of ValuesFactory ValueDescriptionAddress
Type of sensor connected to input 10 – 1700: Sensor is not connected; 1: Sensor with output 0 – 10 V; 2: Sensor with output 2 – 10 V; 3: Sensor with output 0 – 20 mA; 4: Sensor with output 4 – 20 mA; 5: Discrete breaker; 6: Temperature NTC 2 kΩ (B=3950); 7: Temperature NTC 2.5 kΩ (B=3660); 8: Temperature NTC 2.5 kΩ (B=3980); 9: Temperature NTC 5 kΩ (B=3300); 10: Temperature NTC 5 kΩ (B=3520); 11: Temperature NTC 5 kΩ (B=3970); 12: Temperature NTC 6.8 kΩ (B=3520); 13: Temperature NTC 10 kΩ (B=3435); 14: Temperature NTC 10 kΩ (B=3650); 15: Temperature NTC 10 kΩ (B=3950); 16: Temperature NTC 15 kΩ (B=4145); 17: Temperature NTC 20 kΩ (B=4200)580
Effective minimum value for sensor of input 1-32768 – +327670For the sensor with analog output – the value of register of effective value (address 141) at minimal value of sensor output (depending on the type); For the discrete breakers – the value of the register of effective value at contacts being open; For temperature sensors – the sensor temperature values (address 140), for which the correction is made581
Effective maximum value for sensor of input 1-32768 – +32767100For the sensor with analog output – the value of register of effective value (address 141) at maximal value of sensor output (depending on the type); For the discrete breakers – the value of the register of effective value at contacts being closed; For temperature sensors – sensor corrected temperature value (address 141), at measured temperature equal to the value of register 581582
Presentation value of sensor 10 – 100: Measured value is presented on the display console and at the status page of WEB-interface; 1: Adjusted value is presented on the display console and at the status page of WEB-interface583
Quantity of decimal signs of adjusted value of sensor 10 – 40The parameter is not used if presentation of measured value has been selected. When adjusted value is presented on the display console or at the status page of WEB-interface, this parameter indicates accuracy of the decimal fraction (position of decimal point from the right edge)584
Annexation of a measuring device of adjusted value of sensor 1-24 – +240The parameter is not used if presentation of measured value has been selected. When adjusted value is presented on the display console or at the status page of WEB- interface, a corresponding annex is presented after the value (0 – no annex): -24: «i»; -21: «z»; -18: «a»; -15: «f»; -12: «p»; -9: «n»; -6: «µ»; -3: «m»; -2: «s»; -1 «d»; 1: «yes»; 2: «g»; 3: «k»; 6: «М»; 9: «G»; 12: «T»; 15: «P»; 18: «E»; 21: «Z»; 24: «I»585
Measuring device of effective value of sensor 1 for imagingLine of symbols%The parameter is not used if presentation of measured value has been selected. When adjusted value is presented on the display console or at the status page of WEB-interface, the value a corresponding is presented after annex.586 – 589
Type of sensor connected to input 20 – 170Similar to 580590
Effective minimum value for sensor of input 2-32768 – +327670Similar to 581591
Effective maximum value for sensor of input 2-32768 – +32767100Similar to 582592
Presentation value of sensor 20 – 10Similar to 583593
Quantity of decimal signs of adjusted value of sensor 20 – 40Similar to 584594
Annexation of a measuring device of adjusted value of sensor 2-24 – +240Similar to 585595
Measuring device of effective value of sensor 2 for imagingLine of symbols%Similar to 586 – 589596 – 599
Type of sensor connected to input 30 – 170Similar to 580600
Effective minimum value for sensor of input 3-32768 – +327670Similar to 581601
Effective maximum value for sensor of input 3-32768 – +32767100Similar to 582602
Presentation value of sensor 30 – 10Similar to 583603
Quantity of decimal signs of adjusted value of sensor 30 – 40Similar to 584604
Annexation of a measuring device of adjusted value of sensor 3-24 – +240Similar to 585605
Measuring device of effective value of sensor 3 for imagingLine of symbols%Similar to 586 – 589606 – 609
Type of sensor connected to input 40 – 170Similar to 580610
Effective minimum value for sensor of input 4-32768 – +327670Similar to 581611
Effective maximum value for sensor of input 4-32768 – +32767100Similar to 582612
Presentation value of sensor 40 – 10Similar to 583613
Quantity of decimal signs of adjusted value of sensor 40 – 40Similar to 584614
Annexation of a measuring device of adjusted value of sensor 4-24 – +240Similar to 585615
Measuring device of effective value of sensor 4 for imagingLine of symbols%Similar to 586–589616 – 619
ParameterRange of ValuesFactory ValueDescriptionAddress
Enable periodic automatic restart of the device0 – 110: periodic restart disabled; 1: device restarts at a specified interval of time630
Device restart interval, min5 – 7200120Used if periodic restart of the device is enabled631
Enable the mode of automatic restart only when there are no connections0 – 11Used if periodic automatic restart of the device is enabled. 0: device restarts at a specified interval of time after startup; 1: device restarts at a specified interval of time after the last transmitting via Ethernet or GSM networks632
MODBUS exception code generated when there is no access0 – 25510: When there is no access to device MODBUS registers or connected devices, the reply is not returned to the client. 1-255: When there is no access to the client sending the inquiry, this exception code is returned633
MODBUS exception code generated when there is no reply0 – 255110: When there is no reply from inquiry addressee (Gateway Timeout) the reply is not returned to the client; 1-255: when there is a reply from the inquiry addressee, this exception code is returned to the client634
Switch on normally closed relays only after device complete initialization0 – 100: normally closed relays are switched on immediately after device start; 1: normally closed relays are switched on only after device initialization procedure (it is recommended, if relay outputs are connected with universal inputs)635
MODBUS exception code generated if there is no connection to query addressee0 – 255100 – If there is no connection to the query addressee (Gateway Path Unavailable), response is not returned to the client; 1 – 255 – if there is no connection to the query addressee, this exception code is returned to the client636
Enable RS-485 slave mode0 – 100 – Driving mode (Master). RS-485 is used to send queries; 1 – Driven mode (Slave). RS-485 is used to receive queries from additional client637
First MODBUS-identifier of RS-4851 – 2551Parameters define a range of MODBUS identifiers used for RS-485. In the master mode the queries with addresses in this range (and also the broadcast ones with address 0) are sent via RS-485. In the slave mode the queries with addresses in this range (and also the broadcast ones and the queries to EM-486 address) are received via RS-485638
Last MODBUS-identifier of RS-4851 – 255255See register 638639

Connection to the First Remote Server of MODBUS TCP

Section titled “Connection to the First Remote Server of MODBUS TCP”
ParameterRange of ValuesFactory ValueDescriptionAddress
IP-address of remote serverIP-address192.168.0.112It is used when enabling redirection of queries to MODBUS TCP remote server. IP-address of the remote server wherewith connection is maintained640 – 643
Port of the remote server connection0 – 65535502It is used during redirection of queries to the remote server. The remote server port is for MODBUS TCP connection644
Standby time to answer from the remote server, ms0 – 600001000It is used during redirection of queries to the remote server. After the query transfer, if the correct answer failed to be received within this time interval, answer waiting is stopped645
Standby time to repeated connection to the remote server, ms0 – 24020It is used during redirection of queries to the remote server. After connection with the server is lost, the repeated connection will be performed after preset standby time646
Remote server connection mode0 – 800 – MODBUS TCP remote server is not used; 1 – to connect to the server using Ethernet or GPRS, preferably via Ethernet; 2 – to connect to the server using Ethernet or GPRS, preferably via GPRS; 3 – to connect to the server only via Ethernet; 4 – to connect to the server only via GPRS; 5 – similar to 1 with virtual identifiers; 6 – similar to 2 with virtual identifiers; 7 – similar to 3 with virtual identifiers; 8 – similar to 4 with virtual identifiers647
First MODBUS-identifier of the remote server1 – 2551It is used during redirection of queries to the remote server. The parameters define the range of MODBUS identifiers used on the remote server. Queries with addresses in this range (and also the broadcast ones with address 0) are sent to the remote MODBUS TCP server648
Last MODBUS-identifier of the remote server1 – 255255See register 648649
ParameterRange of ValuesFactory ValueDescriptionAddress
Pulse counter mode for input 10 – 700 - counter not used; 1 - pulse rising edge counter; 2 - pulse falling edge counter; 3 - both pulse edges counter; 4 - similar to 0; 5 - similar to 1, the counter is saved to the memory card; 6 - similar to 2, the counter is saved to the memory card; 7 - similar to 3, the counter is saved to the memory card650
Pulse quantity in device of time of counter 11 – 9999999998000Used only is counter is switched on. Pulse quantity on input, after pulses are registered counter is set to one651 – 652
Counter 1 maximum value0 – 999999999999999999Used only is counter is switched on. After counter maximum value exceeds counter is set to 0653 – 654
Counter 1 maximum frequency1 – 500000500000Used only is counter is switched on. Square pulses maximum frequency on input. For pulses of other form value shall be increased655 – 656
Lower threshold for determining the edge of the pulse for counter 10 – 10025Used only is counter is switched on. Falling edge start is defined when signal weakens on input at lower threshold. Threshold is set as a share from peak signal in percentages657
Upper threshold for determining the leading edge for counter 10 – 10075Used only is counter is switched on. Rising edge start is defined when signal enhances on input at higher threshold. Threshold is set as a share from peak signal in percentages658
Pulse counter mode for input 20 – 70Similarly 650660
Pulse quantity in device of time of counter 21 – 9999999998000Similarly 651 – 652661 – 662
Counter 2 maximum value0 – 999999999999999999Similarly 653 – 654663 – 664
Counter 2 maximum frequency1 – 500000500000Similarly 655 – 656665 – 666
Lower threshold for determining the edge of the pulse for counter 20 – 10025Similarly 657667
Upper threshold for determining the leading edge for counter 20 – 10075Similarly 658668
Pulse counter mode for input 30 – 70Similarly 650670
Pulse quantity in device of time of counter 31 – 9999999998000Similarly 651–652671 – 672
Counter 3 maximum value0 – 999999999999999999Similarly 653–654673 – 674
Counter 3 maximum frequency1 – 500000500000Similarly 655–656675 – 676
Lower threshold for determining the edge of the pulse for counter 30 – 10025Similarly 657677
Upper threshold for determining the leading edge for counter 30 – 10075Similarly 658678
Pulse counter mode for input 40 – 30Similarly 650680
Pulse quantity in device of time of counter 41 – 9999999998000Similarly 651–652681 – 682
Counter 4 maximum value0 – 999999999999999999Similarly 653–654683 – 684
Counter 4 maximum frequency1 – 500000500000Similarly 655–656685 – 686
Lower threshold for determining the edge of the pulse for counter 40 – 10025Similarly 657687
Upper threshold for determining the leading edge for counter 40 – 10075Similarly 658688

Automatic Transition to Daylight Saving Time

Section titled “Automatic Transition to Daylight Saving Time”
ParameterRange of ValuesFactory ValueDescriptionAddress
Daylight saving time transition mode0 – 1500 – automatic transition is not used (the gain can be set manually when setting the clock); 1 – Brazil; 2 – Great Britain; 3 – Germany; 4 – Greece; 5 – Jordan; 6 – Italy; 7 – Namibia; 8 – Poland; 9 – Portugal; 10 – USA; 11 – Turkey; 12 – Namibia; 13 – Finland; 14 – France; 15 – according to preset days700
Preset month for transition to daylight saving time1 – 123It is used if you selected the automatic transition to daylight saving time on the specified days. The month when the clock will be set one hour ahead701
Preset week of the month for transition to daylight saving time1 – 1010It is used if you selected the automatic transition to daylight saving time on the specified days. Week of the month when the clock will be set one hour ahead. 1–5 – week of the month, counting the part weeks; other values – the last week of the month702
Preset the week day for transition to daylight saving time1 – 77It is used if you selected the automatic transition to daylight saving time on the specified days. The week day when the clock will be set one hour ahead703
Preset hour for transition to daylight saving time0 – 222It is used if you selected the automatic transition to daylight saving time on the specified days. The hour of the day at which the clock will be set one hour ahead704
Preset month of revert to standard time1 – 1210It is used if you selected the automatic transition to daylight saving time on the specified days. The month when the clock will be set one hour back705
Preset week of the month of revert to standard time1 – 1010It is used if you selected the automatic transition to daylight saving time on the specified days. Week of the month when the clock will be set one hour back. 1–5 – week of the month, counting the part weeks; other values – the last week of the month706
Preset day of the week of revert to standard time1 – 77It is used if you selected the automatic transition to daylight saving time on the specified days. The day of the week when the clock will be set one hour back707
Preset hour of revert to standard time1 – 233It is used if you selected the automatic transition to daylight saving time on the specified days. The hour of the day at which the clock will be set one hour back708
ParameterRange of ValuesFactory ValueDescriptionAddress
Sunny day0 – 310 – official; 1 – civil; 2 – nautical; 3 – astronomical709
Latitude, degrees0 – 8946The absolute value of the latitude710
Latitude, minutes0 – 5929Minutes of latitude711
Latitude, seconds0 – 5910Seconds of latitude712
Longitude, degrees0 – 17930The absolute value of the longitude713
Longitude, minutes0 – 5943Minutes of longitude714
Longitude, seconds0 – 5940Seconds of longitude715
Quadrant0 – 300 – N latitude, E longitude; 1 – N latitude, W longitude; 2 – S latitude, E longitude; 3 – S latitude, W longitude716

The Connection to the Server of NTP Clock Synchronization

Section titled “The Connection to the Server of NTP Clock Synchronization”
ParameterRange of ValuesFactory ValueDescriptionAddress
NTP server connection mode0 – 400 – clock synchronization with the server is not used; 1 – to connect to the servers using Ethernet or GPRS, preferably via Ethernet; 2 – to connect to the servers using Ethernet or GPRS, preferably via GPRS; 3 – to connect to the servers only via Ethernet; 4 – to connect to the servers only via GPRS717
Time period of connection to NTP servers, h1 – 24024It is used if you have enabled synchronization of clocks with the server clock. The time interval over which the server time is received718
Minimum shift of clock for synchronization, s1 – 1802It is used if you have enabled synchronization of clocks with the server clock. The synchronization is performed after receiving the server time, if the difference between the clocks is no less than this value719
ParameterRange of ValuesFactory ValueDescriptionAddress
Supply voltage minimum for safe memory card removal, mV0 – 240009000If the supply voltage is below the specified value, the memory card will be safely removed. The card can be used again after the supply voltage exceeds the minimum plus 0.5 V. 0 - do not remove the memory card, even if the supply voltage is unknown724
Format for logging parameters in task files0 – 41Used if there is a memory card and logging actions in task files. 0 - not used; 1 - compact file of data bytes; 2 - CSV table with text separator; 3 - similarly 2 with a separator; 4 - similar to 2 with tab delimiter725
Maximum size of log files, kB0 – 6553565535Used if there is a memory card present, logging actions in task files, and logging is enabled. The size of the generated files is limited to the specified size plus 1 kB726
Minimum stored period in recorder mode, days0 – 25530Used if there is a memory card present, logging actions in task files, and logging is enabled. 0-183 - the oldest files (older than the specified number of days ago) can be deleted to write new data; Other values - old files are saved, new data recording is suspended when the memory card is full727
ParameterRange of ValuesFactory ValueDescriptionAddress
Communication channel encryption with MODBUS TCP clients0 – 21Used for connections to MODBUS TCP ports (reg. 334 and 450). 0 - disabled; 1 - optional (enabled at the client’s request, if the client supports encryption); 2 - forced (commands and data are blocked, except those necessary to start the encrypted channel)728
MODBUS identifier of the first remote server compatible with Novatek-Electro gateways0 – 2550Used only when connection to a remote server is selected. Virtual ID mode, if enabled for the server, is not reflected in this parameter. 0 - features for compatible gateways are disabled (recommended if compatibility is unknown); 1-255 - channel encryption (reg. 731), password sending for access (reg. 800-809) are available; if disabling of inactive clients (reg. 451) is selected, short requests are sent during downtime to maintain the connection730
Encryption of communication channel with the first remote MODBUS TCP server0 – 21Used only if connection to a remote server is selected and its identifier is set (reg. 730). 0 - disabled; 1 - optional (enabled if the server supports encryption); 2 - forced (the connection is disconnected if the encrypted channel could not be established)731
MODBUS identifier of the second remote server0 – 2550Similar to 730732
Encryption of communication channel with the second remote server MODBUS TCP0 – 21Similar to 731733
MODBUS identifier of the third remote server0 – 2550Similar to 730734
Encryption of communication channel with the third remote MODBUS TCP server0 – 21Similar to 731735
ParameterRange of ValuesFactory ValueDescriptionAddress
Main subscriber phone numberCharacter string-Can be used to send SMS. Up to 20 characters. There can be no spaces in the line740 – 759

Connect to the Second Remote MODBUS TCP Server

Section titled “Connect to the Second Remote MODBUS TCP Server”
ParameterRange of ValuesFactory ValueDescriptionAddress
Remote server IP addressIP-address192.168.0.113Similar to 640 – 643760 – 763
Remote server connection port0 – 65535502Similar to 644764
Waiting time for a response from a remote server, ms0 – 600001000Similar to 645765
Waiting time before reconnecting to a remote server, ms0 – 24020Similar to 646766
Remote server connection mode0 – 80Similar to 647767
First MODBUS-identifier of the remote server1 – 2551Similar to 648 – 649768
Last MODBUS-identifier of the remote server1 – 255255See register 768769

Connection to the Third Remote MODBUS TCP Server

Section titled “Connection to the Third Remote MODBUS TCP Server”
ParameterRange of ValuesFactory ValueDescriptionAddress
IP address of the remote serverIP address192.168.0.113Similar to 640 – 643770 – 773
Remote server connection port0 – 65535502Similar to 644774
Response time from remote server, ms0 – 600001000Similar to 645775
Waiting time before reconnection to the remote server, ms0 – 24020Similar to 646776
Remote server connection mode0 – 80Similar to 647777
First MODBUS-identifier of the remote server1 – 2551Similar to 648–649778
Last MODBUS-identifier of the remote server1 – 255255See register 778779

Preset Passwords for Access to Remote Servers

Section titled “Preset Passwords for Access to Remote Servers”
ParameterRange of ValuesFactory ValueDescriptionAddress
Preset password for access to the first remote MODBUS TCP serverCharacter string-Used only if connection to a remote server is selected and its ID is set (reg. 730). If a password is set, it will be entered immediately after connecting to the server. Obtained access rights depend on the settings of the remote server. A string up to 10 characters long can be specified as a password. No spaces can be in the string800 – 809
Preset password for access to the second remote MODBUS TCP serverCharacter string-Similar to 800 – 809810 – 819
Preset password for access to the third remote MODBUS TCP serverCharacter string-Similar to 800 – 809820 – 829
ParameterRange of ValuesFactory ValueDescriptionAddress
User’s settings and stored values0 – 655350They can be used to store any identification data of the device or for adjusting the settings of task files operation5250 – 5499
ParameterRange of ValuesFactory ValueDescriptionAddress
Adding daylight saving time, min-1440 – +1440-Current gain. It is set during manual transition to the daylight saving time, when selecting the automatic mode it will be adjusted within 5 minutes. The value must be a multiple of 1534817
Adding time zone, min-1440 – +1440120It is used during synchronization of the clock with the server clock. The value must be a multiple of 1534818
Second0 – 59-The time is to be set at the clock34819
Minute0 – 59-The time is to be set at the clock34820
Hour0 – 23-The time is to be set at the clock34821
Day1 – 31-The date is to be set at the clock34822
Month1 – 12-The date is to be set at the clock34823
Year0 – 65535-The year is to be set at the clock34824
Set the clock0 – 655350It is used to set the clock. When recording to this register with any value, the new clock settings in registers 34817-34824 will be set34825