Перейти до вмісту

EXT0003: Device Journal

Цей контент ще не доступний вашою мовою.

  • Extension dependencies: EXT000F
  • Document status: Testing

This extension describes reading and clearing the journal of accumulated data (typically measurement history).

<DATE> (<VAL> ...)
FieldLengthDescription
DATE4 bytesUnix timestamp (seconds since 1970-01-01 UTC)
VALvariableTracked parameter values (device-specific)

All journal entries have the same length within a session.

Read tracked parameter values. Returns maximum records that fit in response.

Request:

<TID> 3900 0006 0005 <AFTERREC>

Response:

<TID> 3900 <LEN> 0005 <LASTREC> [<RECORDS>]
FieldLengthDescription
AFTERREC4 bytesLASTREC from previous packet (0 for first request)
LASTREC4 bytesAddress of last entry in current packet
RECORDSvariableJournal entries (descending date order)

Errors:

CodeDescription
0010ROM read error
0011Invalid AFTERREC

Clear all journal contents. Starts asynchronous process (use 0019 for result).

Request:

<TID> 3900 0002 0006

Response:

<TID> 3900 <LEN> 0006 <PROCID> [<BUSYTIME>]
FieldLengthDescription
PROCID2 bytesProcess ID for result query
BUSYTIME4 bytesMax time if not background

Process Errors:

CodeDescription
0010ROM write error
0011ROM resource expired